CF1200 has been designed for use in counterflow cooling towers for commercial HVAC and light industrial applications.
It is a honeycomb modular block design that is light and easy to handle for ongoing maintenance.
- Water Quality: Best suited for applications with low TSS, typically less than 25 PPM.
- Microbiological Control: Requires good water treatment with microbiological control (less than 1 PPM where control is poor).
- Source Water: Suited for make-up water derived from potable or filtered water sources.
- Chemical Treatment: Water treatment must include an oxidizing biocide and appropriate scale inhibitors.
- Location/Environment: Tower location should be areas with minimal to moderate airborne dust levels.
Oil or grease potential contamination needs to be maintained at less than 5 PPM and the water treatment requires appropriate surfactant use.
Key Benefits:
Product Specifications
| Length | 1220mm (4ft) - 1830mm (6ft) and 2440mm (8ft) |
|---|---|
| Width and Height | 305mm x 305mm |
| Sheet Spacing | 12mm |
| Thickness | 0.25mm |
| Material | PVC |